| Industrial
Process Controllers & Monitors
alpha-CON500
1/4-DIN 2-Wire Conductivity Transmitter with LCD
This
isolated output 4-20mA industrial transmitter is a sturdy microprocessor-based
instrument that measures conductivity and temperature and transmits
its output via the 2-wire power supply loop. This transmitter has
many user-friendly features – all of which are completely accessible
through the water-resistant membrane keypad.
Ideal for connecting
to a PLC for advanced control systems it can also be connected to
a recorder for a low-cost documentation system. The instrument's housing
is designed with mounting holes for easy installation on plates, poles
or walls. Other features include:
-
User-Customization
through Setup Menu offers flexibility in matching the
transmitter‘s functions to
suit individual‘s specific requirements
-
One-Point
Online Calibration without shutting down the line
-
Output
Current Indicator for Out-of-Range and Hold Conditions
to avoid discrepancy in readings
-
Scaleable
4 to 20 mA Output for better output resolution for chart
recording and other peripheral devices
-
Nonvolatile Memory retains all stored parameters
and calibration data, even if power fails
-
Large
Dual Display shows conductivity and temperature simultaneously—features
clear multiple icons, set points, and status messages
-
Panel-
or Wall-Mount NEMA 4X Weatherproof Housing for outdoor
or indoor installation
-
DC
Power Operation ideal for use in power plants and commercial
sites; can be installed in serial loop.
Specifications of alpha-CON500
Cell
Constant
(K) |
Conductivity
Range
(r1 to r6) |
Resolution |
0.1, 1.0
0.1, 1.0, 10.0
0.1, 1.0, 10.0
0.1, 1.0, 10.0
0.1, 1.0, 10.0
1.0, 10.0 |
Range 1 =
0 – 19.99 uS/cm
Range 2 = 0 – 199.9 uS/cm
Range 3 = 0 – 1999 uS/cm
Range 4 = 0 – 10.00 mS/cm
Range 5 = 0 – 19.99 mS/cm
Range 6 = 0 – 199.9 mS/cm |
0.01 uS
0.1uS
1 uS
0.01 mS
0.01 mS
0.1 mS |
| Temperature
Range |
0-100 °C |
| Temperature
Resolution |
0.1 °C |
| Temperature
Relative Accuracy |
±
0.5 °C |
| Temperature
Compensation |
Auto (Pt
100) (from 0 to 100 °C)
Manual (from 0 to 100 °C) |
| Temperature
Coefficient Factor Setting |
0 to 10% |
| Normalization
Temperature Setting |
25.0 °C
or 20.0 °C |
| Number of
calibration points |
1 |
| Output |
4.0 to 20.0
mA |
Over- / Under
range current output
(Only applicable in the uS range) |
‘ON’
Select - 3.8 mA
‘OFF’ Select - 4 mA (under-range) & 20 mA
(over-range) |
| HOLD current
output |
‘ON’
Select - 22 mA
‘OFF’ Select - Last measured current value |
| Display |
Custom Dual
LCD |
| Averaging/Stability
(READY indicator) |
Yes |
| Operating
Temperature |
0 to 100
°C |
| Power Requirements |
12 to 24
VDC |
| Load Resistance |
Max. 600
Ohm |
| Dimension
/ Weight |
96 x 96 x
66 mm / 210 g |
Assembly
Accessories
| Product Description |
Order Code |
Conductivity
cell, Epoxy body, Graphite sensor, w/3-wire
Pt100, k = 0.1 |
ECCONSEN89X |
Conductivity
cell, Epoxy body, Graphite sensor, w/3-wire
Pt100, k = 1.0 |
ECCONSEN88X |
Conductivity
2 Cell type probe, up to 20µS; Cell constant,
K=0.01 with integrated Pt 100, Material SS316 and 25ft
cable (open-ended) |
EC-CS10-0-01S |
Conductivity
2 Cell type probe, up to 20µS; Cell constant,
K=0.01 with integrated Pt 100, Material Titanium and 25ft
cable (open-ended) |
EC-CS10-0-01T |
Conductivity
2 Cell type probe, 0.1 - 200µS; Cell
constant, K=0.1 with integrated Pt 100, Material SS316
and 25ft cable (open-ended) |
EC-CS10-0-1S |
Conductivity
2 Cell type probe, up to 200 mS; Cell
constant, K=1.0 with integrated Pt 100, Material SS316
and 25ft cable (open-ended) |
EC-CS10-1-0S |
Note: Please contact your authorised distributor or dealer for
the prices of extension measuring cables and other accessories like
tee joints, electrode assembly, and calibration solutions.

 
Thermo
Fisher Scientific Inc.
Copyright © 1997 Eutech Instruments Pte Ltd. 4info@eutechinstamerica.com
|